Longevity - Cycle lifetime up to 5,000 times
Stability - Made with safest LiFePO4 (LFP) cell chemistry - highly stable, no thermal runaway
All-encompassing - Three-level BMS system ensures dependability
Safety - Integrated fire extinguishing system on battery module level - precise & quick fire control, non-proliferation
Flexibility - Active current balance control supports new and used battery cabinet combinations
Intelligence - Active voltage balance control allows for battery strings of different numbers to be connected in parallel with each-other
Cost-effective - Automatic grouping and capacity checks cut manual capacity test costs and avoid power failure risks
70% less footprint - high power density means a significant space saving
80% less operating and maintenance (O&M) costs thanks to its smart BMS
Items |
Discription |
---|---|
Product model |
LI-Ion Data Center 1.0 |
Battery cell material |
LiFePO4 |
Charging current |
≤ 1C, 0.5C by default |
Cycle life |
Up to 5000 cycles @ 50 % DoD @ 25 °C |
Nominal capacity |
162 Ah / 62.20 kWh [6+6] – 162 Ah / 72.57 kWh [7+7] – 162 Ah / 82.94 kWh [8+8] |
Capacity for calculating the backup time * |
153 Ah / 58.75 kWh [6+6] – 153 Ah / 68.54 kWh [7+7] – 153 Ah / 78.33 kWh [8+8] |
Weight |
900 kg [6+6] – 1000 kg [7+7] – 1100 kg [8+8] |
Dimension (W*D*H) |
600 x 850 x 2000 mm |
Self discharge |
≤5 % / 3 months @ 0 to 30 °C |
Fire protection |
Module-level: Perfluorohexanone fire suppression fluid |
Communication interface |
RS485, Dry contacts, TCP IP, MODBUS on RS485 & MOBUS over TCP IP |
Protection |
Over temperature, over current, short circuit, overcharge, discharge, etc. |
Charge voltage |
2.30Vpc @ 25 °C – 32 AGM to 50 AGM blocks – 442V to 690V depending on the configuration |
Discharge capability |
1C to 6C: 60 min @ 50 kW or 10 min @ 300 kW ([7+7] cabinet from 16 to 30 °C) |
IP Protection level |
IP21 according to IEC60529 standard |
Mounting type |
Against the wall, reserve at least 800 mm from the front |
Storage temperature |
0 °C to 40 ºC |
Transportation temperature |
-40 °C to 60 ºC |
Operating temperature |
0 °C to 40 ºC (20 to 25 °C is recommended) |
Relative humidity |
5 % to 95 % (no condensation) |
Max. operating altitude |
4000 m, derating is required if the altitude exceeds 1000 m |
Heat dissipation at rated power |
[8+8] cabinet: 2.65kW - [7+7] cabinet: 2.35kW - [6+6] cabinet: 2.05kW |